Permit Number: 03 6084
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3901 OLD SEWARD HWY Anchorage
Location:
Work Description: Work Descr: Tenant improvement, Remarks: gjs
Status: Closed
Project Name: SADLERS HOME FURNISHING
Review Type: Architectural
Result: Approved
Result Date: 12/4/2003 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): Thank you for taking the time to meet with us this morning and bringing forward your design to be reviewed for build code compliance. In addition to the items addressed this morning during our meeting, please include the following issues as part of the comments as these issues may require your attention for code compliance or additional clarification. If you have any questions regarding these comments please feel free to call me at 343-8183: C(2): Please Reference number of exits for the Discount section 101: Please clarify if the opening in the wall locatedbetween the Discount rooms 117 and 101 is a door way. Please also review the occupant load calculations for the Discount room 101, as I find that for occupant loads greater than 50, section 1004 requires that at least two exists must be provided. Please review and address.