Permit Number:
03 5618
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
1700 HILLCREST DR Anchorage
Location:
Work Description:
Work Descr: renovate 2 sets of restrooms, and boys and girls lockerrooms, Remarks: gjs
Status:
Closed
Project Name:
WEST HIGH SCHOOL
Review Type:
Architectural
Result:
Approved
Result Date:
7/16/2003 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): The following comments are based on the 2000 International Building Code (IBC) and must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations. C(2): Reference the accessible toilet compartments. The door shall be hinged 4 inches maximum from the adjacent wall or partition farthest from the water closet in accordance with ICC/ANSI A117.1, section 604.8.2 per IBC section 1101.2. RESOLVED 7-16-03 PER REVISED PLANS.