Permit Number:
03 5317
Permit Type:
Commercial Building Permit - None BldgAdd
Address:
3901 OLD SEWARD HWY Anchorage
Location:
Work Description:
Work Descr: 27441 sq ft First Floor, 8294 sq ft Second floor, Type II-B , Airconditioned, sprinklered, Remarks: cm
Status:
Closed
Project Name:
SADLERS STOCKROOM
Review Type:
Structural
Result:
Approved
Result Date:
10/16/2003 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): This review is for various RFI's submitted 9/25/03 that involve changes to the plans. Comments below are referenced by SKS #. APPROVED 10/16/03 CSK C(2): See SKS 21: Please provide a check for "web" (in this case the flange) strength for the flat track and studs at concentrated loads from the hoist beam. Check the "T" sections directly under beam as well as the "S" sections at mid height of the wall. RESOLVED 10/16/03 CSK