Address: 3901 OLD SEWARD HWY Anchorage
Location:
Work Description: Work Descr: 27441 sq ft First Floor, 8294 sq ft Second floor, Type II-B , Airconditioned, sprinklered, Remarks: cm
Status: Closed
Project Name: SADLERS STOCKROOM
Review Type: Structural
Result: Approved
Result Date: 7/16/2003 12:00:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): This review is based on the requirements of the 2000 International Building Code and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. APPROVED FOR PERMIT 7/16/03 CSK C(2): Reference Sheet S1.3.1: Please clarify on the plans or in details the base plate elevation for HSS exterior columns (at top of grade beam or top of slab?- anchor bolts embedded 4" or 12" into grade beam?). In Detail 2/S1.2.2, "top of footing " callout should read "top of grade beam". RESOLVED PENDING ADDING INFORMATION TO THE PLANS 5/29/03 CSK