Permit Number:
03 5317
Permit Type:
Commercial Building Permit - None BldgAdd
Address:
3901 OLD SEWARD HWY Anchorage
Location:
Work Description:
Work Descr: 27441 sq ft First Floor, 8294 sq ft Second floor, Type II-B , Airconditioned, sprinklered, Remarks: cm
Status:
Closed
Project Name:
SADLERS STOCKROOM
Review Type:
Mechanical
Result:
Approved
Result Date:
6/26/2003 12:00:00 AM
Comments:
Code Section
Review Comment
Status
Advisory Information:
. C(1): The following comments based on the 2000 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations. C(2): Reference RTU-1. Please verify compliance with IFGC section 611.5 which requires 4 cfm of outside air per 1000 btuh input. Since both the gas burner and outside air modulate, this requirement must be met throughout the entire range of operation. RESOLVED 6-26-03 PER ENGINEER'S VERIFICATION.