Permit Number: 01 5277
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2741 DEBARR RD Anchorage
Location:
Work Description: Work Descr: t/i, Remarks: td
Status: Closed
Project Name:
Review Type: Plumbing
Result: Approved
Result Date: 5/4/2001 8:58:10 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): The following comments based on the 1997 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications doesnot permit the violation of any section of the Uniform plumbing Code or any federal, state or local regulations. C(2): 020-M2: Reference the vacuum piping. The minimum allowable pipe size is one inch per table 13-6. RESOLVED 5-4-01. PIPES SIZED PER NFPA 99, SECTION 4-9.1.1.1.