Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): Please provide 20 minute door in the corridor at grid line 3. Door schedule do not list BR, do you mean AR? UBC 1004.3.4.3.2.1 C(2): Please update drawing 020-A2.1 to show B occupancy works for pre/post-op areas 1 and 2. By definition UBC 308.1 Division I-1.2 occupancy would apply for more then 5 tenant spaces with patient incapable of unassisted self-preservation. The I-1.2/B occupancy separation requirement is 2 hours and the I-1.2/S-3 separation is 4 hours.