Permit Number: 00 6151
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3101 PENLAND PKWY Anchorage
Location:
Work Description: Work Descr: T.I., Remarks: mw 8-14-01 Electric Inc is no longer the contractor for installing the fire alarm it will be Anderson Electric-cah
Status: Closed
Project Name: SOUTHCENTRAL FOUNDATION EARLY
Review Type: Mechanical
Result: Approved
Result Date: 12/28/2000 11:19:44 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

. C(1): The following comments based on the 1997 edition of the Uniform MECHANICAL Code should be resolved before a permit is issued. This correction list is not a building permit. The approval of plans and specifications does not permit the violation of any section of the Uniform MECHANICAL Code or any federal, state or local regulations. C(2): The dental room must be separated from the rest of the building by a one-hour occupancy separation as shown on the revised Architectural sheets. Therefore combination fire/smoke dampers must be installed on the supply and return duct penetrations. Please verify compliance.