Permit Number: X25-1361
Permit Type: Commercial Building Permit - ChangeOrdr BldgNew
Address: 4960 A ST Anchorage
Location:
Work Description: PRIMARY DECOR COLOR CHANGE, FIXTURE FURNITURE AND EQUIPMENT, FIREPLACE IN LOBBY -SBW
Status: Open
Project Name: Change Order of Bldg App C15-1806
Review Type: Plumbing
Result: Approved
Result Date: 12/3/2025 9:29:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Reviewer: Ross Noffsinger
ross.noffsinger@anchorageak.gov

Status: 5/29/25 Comments to be resolved.

1. Where does Sump Pump P-3 discharge? Please clarify the location, size and capacity of the waste line receiving the discharge.

2. Please confirm Enstar approval of the proposed medium pressure natural gas piping system located inside the building as required by 2018 IFGC Section 23.110.417. Also note the specific requirements.

23.110.417 - Medium pressure gas.
Amend Chapter 4 by adding section 417 as follows:

417.1 Medium pressure gas. The installation of a medium pressure gas system (2 psig or 5 psig) within a building must be pre-approved by the local gas utility. Steel piping shall be welded or assembled with press-connect fittings. Test pressure for all medium pressure gas piping shall be 60 psig.

Exception: Medium pressure gas piping within mechanical rooms housing the equipment being served, shall be threaded, welded, or assembled with press-connect fittings in accordance with IFGC 403.10. Threaded piping and piping assembled with press-connect fittings shall not be concealed within construction.

417.2 CSST medium pressure gas. The installation of a CSST medium pressure gas system (2 psig or 5 psig) within a building must be pre-approved by the local gas utility. Test pressure for all medium pressure gas piping shall be 60 psig. Joints shall be limited to the meter connection and at the regulator to the appliance being served. Intermediate joints are not allowed without prior approval.





2_

Reviewer Trent Seymore 2025.12.03 Wednesday 09:40

1        Resolved. Reference X25-1361 Sheet P1.1 and X18-1936 Sheet PL6 detail 2.

2        Resolved per will serve letter from Enstar.