Permit Number: X25-1361
Permit Type: Commercial Building Permit - ChangeOrdr BldgNew
Address: 4960 A ST Anchorage
Location:
Work Description: PRIMARY DECOR COLOR CHANGE, FIXTURE FURNITURE AND EQUIPMENT, FIREPLACE IN LOBBY -SBW
Status: Open
Project Name: Change Order of Bldg App C15-1806
Review Type: Mechanical
Result: Approved
Result Date: 12/3/2025 9:28:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Reviewer: Ross Noffsinger
ross.noffsinger@anchorageak.gov
343-8309

Status: 5/28/25 - Comments to be resolved.

1. Please clarify/verify the draft inducer is listed in accordance with UL 378 (per 2018 IFGC Section 503.3.3, Item No. 1) and verify theventing system meets both the fireplace and draft inducer installation instructions. Include the fireplace make/model.

2. Please verify compliance with IFGC Section 503.3.3, Item No. 5: Provisions shall be made to prevent flow of gas to the burners when the draft system is not performing so as to satisfy the operating requirements of the appliance for safe performance.



2_

Reviewer Trent Seymore 2025.12.03 Wednesday 09:42

1        Enviro C27I fireplace is tested to ANSI Z21.88 /CSA 2.33 VENTED GAS FIREPLACE HEATERS and CSA 2.17 GAS FIRED APPLIANCES FOR HIGH ALTITUDES.

2        Enviro vertical power vent system (50-4375) is tested to ANSI Z21.88 /CSA 2.33 VENTED GAS FIREPLACE HEATERS and CSA 2.17 GAS FIRED APPLIANCES FOR HIGH ALTITUDES. 