Permit Type: Commercial Building Permit - None BldgAdd
Address: 7012 SAND LAKE RD Anchorage
Location: 7012 SAND LAKE RD
Work Description: EPLANS: NEW 2165 SQ FT COLD STORAGE WAREHOUSE- CCK 
ELECTRONIC FOLDER
Status: Issued
Project Name: EPLANS: FISH & WILDLIFE SERVICE
Review Type: Zoning
Result: Approved
Result Date: 10/21/2025 2:00:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
21.03.080E An amendment to the conditional Use permit is required, contact Community Planning at 343-7931 for details.
///9/28/25 The revised code study does not change the comment; please resolve. tb
///10/21/25 Amendment not required; the proposed use is permitted by right per E. Appleby; see email. tb


2_Resolved
Table 21.06-3, Front, side, and rear setbacks shall be 25ft when the abutting district is DR, PR, PLI or residential; please resolve.
///9/28/25 Plot plan shows an 18ft setback from the building to the property line; please resolve. tb
///10/21/25 see updated plot, site, and civil sheets. tb


3_Zoning review is incomplete pending receipt of requested information, additional comments may result from new information received.Resolved