Permit Number: C25-1300
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 401 6TH AVE Anchorage
Location:
Work Description: EPLANS: CONVERSION OF EXISTING PROPERTY FROM SHERATON TO HYATT; R & R FURNITURE/FIXTURES/ EQUIPMENT OF PUBLIC SPACES. REPLACE MAIN ENTRY DOOR WITH AUTOMATIC SLIDER FOR ADA COMPLIANCE, REPLACE OPERABLE PARTITIONS IN BALLROOMS- CCK
ELECTRONIC FOLDER
***REVIEW FEE'S PAID FOR BY PREMIER DESIGN; THEY ARE AWARE THAT PERMIT FEE'S MUST BE PAID TO ISSUE PERMIT** CCK 3/26/25
PERMIT FEES PAID BY PREMIER -SBW 11/13/25
SAMEDAY ELEC INS PAID FOR E25-1306 ON 12/5/25 - RED
Status: Issued
Project Name: EPLANS: HYATT- 401 E 6TH AVE
Review Type: Electrical
Result: Correction
Result Date: 4/2/2025 10:28:22 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

ELECTRICAL SCOPE OF WORK:
The electrical plans are stamped and signed by a mechanical engineer.                                                                                                                                      
Please provide 100% designed engineered drawing by a registered professional electrical engineer of the State of Alaska. The design shall include, wiring method, home run wiring with type, size of wires and conduits, over-current protection, panel schedules with connected and demand loads and one-line diagram.    