Permit Number: C24-1513
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1602 HILLCREST DR Anchorage
Location:
Work Description: PLACING FOUR RELOCATBALES PER SUBMITTED SITE PLAN - RED
Status: Issued
Project Name: WEST ROMIG - RELOCATABLES
Review Type: Structural
Result: Correction
Result Date: 6/10/2024 1:58:41 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT STATUS
6/10/2024 - Permit reviewed. Comments issued.

1. Per MOA policy relocatable classrooms will note be occupied at wind speeds over 70-mph so tie downs have not typically been required. What is the intent of the tie downs shown in the details? Is it to allow occupancy for higher wind speeds or is it to just tie the buildings down to prevent sliding and/or overturning? Please clarify. If the intent is to allow occupation, calculations will need to be provided to verify these tie downs and the MOA policy should be modified to match the intent of ASD's use of the classrooms. Additional comments may be generated by the response to this comment.