Permit Number: C24-1162
Permit Type: Commercial Building Permit - None BldgAlter
Address: 700 G ST Anchorage
Location:
Work Description: EPLANS - TENANT IMPROVEMENT ON 18TH FLOOR ONLY TO INCLUDE P/M/E - RDO
ELECTRONIC FOLDER, SEE ATTACHMENTS
CRITERION OPENED DEMO PERMIT C24-1167 SEPERATELY BEFORE FEE'S WERE PAID - CCK 2/29/24
Status: Issued
Project Name: EPLANS - TI - 18TH FLOOR ONLY
Review Type: Architectural
Result: Correction
Result Date: 3/27/2024 3:58:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

C24-1162: TI - 18TH FLOOR ONLY has one architectural comment in E-Plans.  There is a comment on Sheet G004 (and below).


Manual Fire Alarm


Revise: "Not required for Group M Based on Occupancy Load per IBC 907.2.7"


To: "A full Fire Alarm System is required for Group B Based on Occupancy Load per IBC 907.2.2"


Note that the only exception to the Fire Alarm requirement for Group B is deleted by local amendment.