C24-1162: TI - 18TH FLOOR ONLY has one architectural comment in E-Plans. There is a comment on Sheet G004 (and below).
Manual Fire Alarm
Revise: "Not required for Group M Based on Occupancy Load per IBC 907.2.7"
To: "A full Fire Alarm System is required for Group B Based on Occupancy Load per IBC 907.2.2"
Note that the only exception to the Fire Alarm requirement for Group B is deleted by local amendment.