IN ORDER TO RECEIVE A CERTIFICATE OF COMPLETION OR OCCUPANCY, APPLICANT SHALL SUBMIT A SIGNED AND NOTARIZED OPERATIONS & MAINTENANCE PLAN AND CIVIL AS-BUILTS AND SCHEDULE A FINAL PDCIVIL INSPECTION.
Please provide building plans for review.
///8/16/23 see building plans. tb
The site plan data on page C4 shows incorrect information regarding lot coverage, building height, setbacks, and landscaping. Please resolve.
///8/16/23 see sheet C4. tb
21.07.040F.4.f. The site plan shall not, unless allowed through an administrative site plan review, designate snow storage areas in required perimeter landscaping, or on required trees. Visual Enhancement (L1) landscaping is required along Lake Otis Parkway. The snow storage area appears to encroach into the required 8ft planting bed.
///8/16/23 existing comment remains. 21.07.040F.4.e., Snow storage shall have a minimum dimension of eight feet to accommodate snow piling from a snow blade. Please provide the dimension no the architectural and civil sheets. tb
///10/19/23 see sheet C4. tb
///8/16/23 sidewalks are required along N Tahiti Loop and Samoa Street; please resolve on architectural and civil sheets. tb
///10/19/23 Please provide a copy of the director's determination to waive the sidewalk requirement. tb
///3/4/24 Sidewalks not required per C. Lyon; see sidewalk waiver in documents folder. tb
The plant schedule on sheet L1 states shrubs are required to meet Title 22 instead of Title 21, please resolve. Also, the landscape plans states to see Note #4, but there is not a Note #4 provided in the notes on sheet L1.
///8/16/23 this comment should be resolved on the landscape plan, and not the architectural plan set. tb
///3/4/24 see revised landscape plan. tb
Visual Enhancement Landscaping (L1) is required along Lake Otis Parkway.
///8/16/23 Although there is a 6ft arterial landscape easement along Lake Otis Parkway, L1 Visual Enhancement landscaping is required. Please show landscaping meets the 8ft planting bed width on the architectural, civil, and landscape sheets. tb
Buffer Landscaping (L2) is required along Samoa Street.
///3/4/24 see sheet L1. tb