Electrical Comments
Reviewed by: David Abuobaid Permit #s: E23-1971
Phone: 343-8333 Date: 10/10/2023
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Dan Woods
Phone: 343-82338
Email: Danial.Woods@muni.org
Project: Baggage Equipment
____________________________________________________________________________________ REQUIREMENT OF ELECTRICAL SCOPE OF WORK:
The plans provided are the manufacture layout for installation. Where is the electrical plans?
Please provide 100% designed engineered drawing by a registered professional electrical engineer of the State of Alaska. The design shall include wiring method, home run wiring with type, size of wires and conduits, over-current protection, panel schedules with connected and demand loads.