Permit Number: X23-1695
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: REPAIR STRUCTURAL SLAB ON GRADE - REINFORCING STEEL - BWP
Status: Closed
Project Name: Change Order of Bldg App C22-1070
Review Type: Structural
Result: Correction
Result Date: 9/21/2023 11:43:38 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

CHANGE ORDER STATUS
9/21/2023 - Change order reviewed. Comments issued

1. The response to the RFI indicates this portion of the slab is a tie. Is this transferring seismic forces? If so ACI 318-14 section 25.4.10.2 does not permit the reduction of the development length for the reinforcement. Please verify the epoxy fully develops the bars into the existing slab if this is a seismic tie.