Permit Number: X23-1623
Permit Type: Commercial Building Permit - ChangeOrdr BldgNew
Address: 1871 ANCHORAGE PORT RD Anchorage
Location:
Work Description: EPLANS - OWNER REQUESTED CHANGES TO REDESIGN A SMALL IT ROOM INTO LARGER COMMUNICATIONS ROOM RESULTING IN INTERIOR CHANGES, REDUCTION OF A BREAK ROOM, REVISED ELECTRICAL TELECOMMUNICATIONS DESIGN, AND MINOR MECHANICAL UPDATES -- JJ 
Status: Closed
Project Name: Change Order of Bldg App C22-1886
Review Type: Electrical
Result: Approved
Result Date: 8/29/2023 1:24:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

GENERATOR (IF THE GENERATOR IS AN EMERGENCY TYPE):
The generator system is not identified to be emergency, or standby. The identification "NEC Code Section" should be on the plans next to the generator. Please identify the generator type. If the generator is an emergency type, provide:
(a)  The emergency Gen Set load shedding. (NEC 700.5(B)).                                                                     
(b)  Circuit and wiring identifications and over-current protection of wiring. (NEC 700.9(A.                                                                                 
(c)  Fuel tank capacity for at least 2-hours of continuous operation. (NEC 700.12(b))                                                                             
(d)  Signage of emergency source. (NEC 700.8(A))

GENERATOR DISCONNECTING MEANS:                                                                                            
Sheet E0.2 (Power Line Diagram - Generator Disconnecting Means). The generator shall be equipped with disconnect lockable in the open position. Provide the size and location of the disconnecting means for the generator. Refer to NEC Section 445.18. Please address.

GENERATOR MOUNTING STRUCTURAL SEISMIC CALCULATIONS:                                                                   
Provide structural, seismic calculations and fastening details for the generator including engineers stamp and signature, for structural review on a deferred submittal basis. Refer to Anchorage Administrative Code AAC 23.10.104.8.1. Please address.