Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C23-1664
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: REMOVAL OF (3) EXISTING UNDERGOUND STORAGE TANKS. THE TANKS WILL BE REPLACED WITH ABOVE GROUND TANKS. THE 3 TANKS ARE LOCATED IN DIFFERENT AREAS: ANC ARFF AIRPORT RECUER AND FIRE FIGHTERS, NORTH TERMINAL APRON, AND B TERMINAL APRON -DW
***Permit came in with incorrect valuation ($780,000).  Correct valuation per email dated 7/20/2023 is $78,000.  Difference in valuation will be refunded once project is closed out.  Refund documentation is in folder - MJD 8/29/2023
Status: Closed
Project Name: ANC UNDERGROUND STORAGE TANK REPLACEMENT
Review Type: Structural
Result: Correction
Result Date: 8/1/2023 10:13:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

1. C7: Provide calculations for the seismic and wind restraint of new storage tanks. Update details as required. Typical comment for both tank types.

2. C7: Add notes for special inspections on concrete pads and post installed anchors of the storage tanks.

3. C6: What is note 1 on C6 referring to?
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS