Permit Number: C22-1610
Permit Type: Commercial Building Permit - Regular FillGrade
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location: SOUTH END
Work Description: 2,822,900 CY YARDS OF GRADING, 782,088 CY FILL-GJS
Status: Issued
Project Name: ANC SOUTH AIRPARK CARGO TERMINAL
Review Type: Fire
Result: Approved
Result Date: 11/1/2022 11:33:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
HYDRANT DECOMMISSIONING -      
Refer to Sheet C103. The spacing of hydrants along this roadway will exceed the permitted spacing for structure protection if this hydrant is removed. No other hydrants along this roadway are being proposed. Please remove the note, or provide justification and a specific request to remove the hydrant from service.     
Reference: IFC Section 105.4.2, C103.1

9/16/22 -  Resolved. Updated plans show relocation of hydrant to the north of the existing location // PANILO


2_Resolved
HYDRANT LOCATION AND FLOW RATE -      
Refer to Sheet C103. The new water service for the building shows (4) hydrants on each side of the building loop. Please notate on the utility plan, or provide separate water service plan and profile drawings. Please also provide hydrant flow rate for the most remote hydrant.     
Reference: IFC Section 507.5, B105.2

9/16/22 - Item to be resolved by AWWU permit review // PANILO