Permit Number: C22-1610
Permit Type: Commercial Building Permit - Regular FillGrade
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location: SOUTH END
Work Description: 2,822,900 CY YARDS OF GRADING, 782,088 CY FILL-GJS
Status: Issued
Project Name: ANC SOUTH AIRPARK CARGO TERMINAL
Review Type: Structural
Result: Correction
Result Date: 10/21/2022 9:52:48 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


PERMIT STATUS

2022/07/15 – Initial review complete. Comments issued.

2022/09/15 – F&G Approved. Comments issued.

2022/10/07 – Updated review. Additional comments issued.

2022/10/20 – Updated review. Additional comments in bold.

 

 

F&G COMMENTS

Note: Resolve the below comments for Fill & Grade approval.

 

1. SPECIAL INSPECTIONS

Please provide a letter from the Owner indicating who they will be hiring to provide the special inspections for this project. The special inspectors must be licensed by the Municipality of Anchorage in the types of inspections to be performed.

[Reference: IBC 2018 § 1704.2, AMC § 23.15.1703.7]

 

            2022/09/15 – Comment resolved. F&G Approved.

 

STRUCTURAL COMMENTS

Note: Resolve the below comments for full permit approval.

 

2. STRUCTURAL CALCULATIONS

Please provide the structural calculations for the work on sheets SS001-SS506. Additional comments may be generated from the review of this information.

 

2022/09/15 – Comment resolved. Additional structural review in progress. See also new Comment No. 4

 

3. CODES

Sheet SS002 lists IBC 2012 as the governing building code. IBC 2018 is presently adopted by the MOA.

 

2022/09/15 – Comment remains. The listed wind speed also isn’t consistent with the MOA Wind Zone Map.

 

2022/10/07 – Response accepted per phone conversation. Please submit updated sheet.

 

2022/10/20 – Comment resolved. Criteria updated.

 

4. PERMIT (2022/09/15)

Is all this associated work intended to be completed under this Fill & Grade permit? Please clarify, or coordinate the type of permit with the Permit Counter.

 

2022/10/07 – Comment resolved.

5. CONCRETE (2022/10/07)

Does the vault concrete qualify as an elevated exposure classification with corresponding additional requirements?

[Reference: ACI 318-14 Table 19.3.1.1, 19.3.2.1]

 

2022/10/20 – Comments No. 5-7 Not addressed

 

6. LOADS (2022/10/07)

a. How were the seismic loads for the platform extension calculated? It’s not clear from the calculation package.

 

b. What loads were applied to the lid of the concrete vaults?

 

2022/10/20 – Comments No. 5-7 Not addressed

 

7. KNEE BRACES (2022/10/07)

Knee braces are considered an OMF system. Please indicate how the connection design complies with AISC 341-16 § E.1.6b.

 

2022/10/20 – Comments No. 5-7 Not addressed.