PERMIT STATUS
2022/07/15 – Initial review complete. Comments issued.
2022/09/15 – F&G Approved. Additional comments in bold.
F&G COMMENTS
Note: Resolve the below comments for Fill & Grade approval.
1. SPECIAL INSPECTIONS
Please provide a letter from the Owner indicating who they will be hiring to provide the special inspections for this project. The special inspectors must be licensed by the Municipality of Anchorage in the types of inspections to be performed.
[Reference: IBC 2018 § 1704.2, AMC § 23.15.1703.7]
2022/09/15 – Comment resolved. F&G Approved.
STRUCTURAL COMMENTS
Note: Resolve the below comments for full permit approval.
2. STRUCTURAL CALCULATIONS
Please provide the structural calculations for the work on sheets SS001-SS506. Additional comments may be generated from the review of this information.
2022/09/15 – Comment resolved. Additional structural review in progress. See also new Comment No. 4
3. CODES
Sheet SS002 lists IBC 2012 as the governing building code. IBC 2018 is presently adopted by the MOA.
2022/09/15 – Comment remains. The listed wind speed also isn’t consistent with the MOA Wind Zone Map.
4. PERMIT (2022/09/15)
Is all this associated work intended to be completed under this Fill & Grade permit? Please clarify, or coordinate the type of permit with the Permit Counter.