Permit Number: X22-1536
Permit Type: Commercial Building Permit - ChangeOrdr BldgCombo
Address: W 601 5TH AVE Anchorage
Location:
Work Description: EPLANS - MECHANICAL, PLUMBING, ELECTRICAL CHANGES TO SEWAGE WET WELL AND PUMP ROOM 59 ASSOCIATED WITH NEW SEWAGE PUMPS AND CONTROLS IN BASEMENT LEVEL OF BUILDING - PNY

Status: Closed
Project Name: EPLANS - Change Order of Bldg App C19-2451
Review Type: Electrical
Result: Approved
Result Date: 9/9/2022 11:18:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

The correction are on the plans. Approved 
---------------------------------------------------------
CLASSIFICATION AREAS “LIFT STATION”:

The plan states "per mechanical only the sump pump is classified, room above sump pump is non-classified" Please show the classification of the lift station sump pumps room. Refer to NFPA 70 NEC Section 500.4B(B), and NFPA 820 Standard for Fire Protection in Wastewater treatment and collection Facilities, 2016 Edition, Chapter 7 for Fire and Explosion Prevention and Protection, and State of Alaska MIPL #3.