Permit Number: C22-1610
Permit Type: Commercial Building Permit - Regular FillGrade
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location: SOUTH END
Work Description: 2,822,900 CY YARDS OF GRADING, 782,088 CY FILL-GJS
Status: Issued
Project Name: ANC SOUTH AIRPARK CARGO TERMINAL
Review Type: Structural
Result: Correction
Result Date: 7/15/2022 9:59:35 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


PERMIT STATUS

2022/07/15 – Initial review complete. Comments issued.

 

 

F&G COMMENTS

Note: Resolve the below comments for Fill & Grade approval.

 

1. SPECIAL INSPECTIONS

Please provide a letter from the Owner indicating who they will be hiring to provide the special inspections for this project. The special inspectors must be licensed by the Municipality of Anchorage in the types of inspections to be performed.

[Reference: IBC 2018 § 1704.2, AMC § 23.15.1703.7]

 

 

STRUCTURAL COMMENTS

Note: Resolve the below comments for full permit approval.

 

2. STRUCTURAL CALCULATIONS

Please provide the structural calculations for the work on sheets SS001-SS506. Additional comments may be generated from the review of this information.

 

3. CODES

Sheet SS002 lists IBC 2012 as the governing building code. IBC 2018 is presently adopted by the MOA.

 

 

 

Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revised drawings. While not required it is extremely helpful to the reviewer if the response indicates where in the submittal each comments has been addressed.

 

All submittals should be sent to the permit manager.