Permit Number: C22-1386
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1700 HILLCREST DR Anchorage
Location: WEST HIGH SCHOOL PHASE II (REF. C21-1333, PH 1)
Work Description: ***THIS PERMIT IS FOR PHASE II OF PERMIT #C21-1333***
DEMO & REPLACE HYDRONIC, DOMESTIC WATER, GAS, AND FDC PIPING; DEMO OF ABANDONED IN-PLACE MECHANICAL & ELECTRICAL. DEMO & REPLACE SLAB WITH FINISHES. - MDR
Status: Closed
Project Name: WEST HIGH SCHOOL: WEST & ROMIG SCHOOL SITE TR 1A
Review Type: Plumbing
Result: Correction
Result Date: 5/6/2022 10:25:41 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Mike Radovan

Phone: 343-8279

Email: Michael.Radovan@anchorageak.gov

Project: WEST HIGH SCHOOL UTILIDOR UPGRADES PH II

Review Number: 488479


1) STATUS: 5/6/2022 Comments to be addressed.


2) The following comments based upon the 2018 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. 


3)  M2.05                     Clarify the required flow settings required for the 3/4" and 1" HWC balancing valves. 


4) M2.07                      Clarify the required flow settings required for the 3/4" and 1" HWC balancing valves. 


5) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.  (23.10.104.8.1)