Permit Number: X22-1225
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: REVISED FIREPLACE LAYOUT-GJS
Status: Closed
Project Name: Change Order of Bldg App C18-1264
Review Type: Mechanical
Result: Approved
Result Date: 5/9/2022 10:48:35 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Anthony Beard

Phone: 343-8181

Email: Anthony.Beard@anchorageak.gov

Project: DIMOND CENTER MALL

Review Number: 487120


1) STATUS: 4/20/2022 Comments to be addressed.                       5/09/2022 APPROVED.


2) The following comments based upon the 2018 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.                    RESOLVED 5/09/2022.


3) M1.2                   This portion of the Dimond Mall is Type 1-A construction where combustible construction is not allowed per IBC 602.2. Please clarify on the drawings.               RESOLVED PER RE-SUBMITTAL RECEIVED 5/04/2022.


4) M1.2                   Upper and lower cabinet enclosure venting is required per the manufactures recommended installation instructions. Provide details.           RESOLVED PER RE-SUBMITTAL RECEIVED 5/04/2022.


5) 1/M1.1                The total gas load from the meter is 1220 CFH. Please clarify.                RESOLVED PER RE-SUBMITTAL RECEIVED 5/04/2022.


6) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.  (23.10.104.8.1)                          RESOLVED 5/09/2022.