Permit Number: C22-1070
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: AIRPORT PARKING GARAGE REHABILITATION TO EXTEND STRUCTURE'S SERVICE LIFE. INCLUDES UPGRADE/IMPROVEMENTS FOR WAY FINDING AND LIGHTING. INCLUDES P/M/E/S - BAB
Status: Closed
Project Name: AIRPORT PARKING GARAGE UPGRADES
Review Type: Traffic Engineering
Result: Correction
Result Date: 5/3/2022 11:12:55 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Spoke with Project Contact and they indicated that the work may impact signage and striping within the garage.  Revise the following sheets to address non compliance with federal ADA standards.  It appears that the property has sufficient ADA spaces if some need to be eliminate to address issues.

1.  Sheets A1.01 and A1.01A.  Accessible spaces along Grid line 1.5 between Grid A to C lack accessible aisle between or adjacent to spaces.  Non van accessible spaces require a 5 foot aisle that can be shared between spaces.  If wider than 8 feet than a no parking signage must be added.

2. Sheets A1.03, A1.03A and A1.03B. Accessible spaces along Grid line 1.5 between Grid A to F  lack accessible aisle between or adjacent to spaces.  Non van accessible spaces require a 5 foot aisle that can be shared between spaces.  If wider than 8 feet than a no parking signage must be added.

3. Sheets A104 and 1.04B. Accessible spaces along Grid line 1.5 between Grid D to F lack accessible aisle between or adjacent to spaces.  Non van accessible spaces require a 5 foot aisle that can be shared between spaces.  If wider than 8 feet than a no parking signage must be added.

Provide a standard ADA marking detail showing typical dimensions and Pavement markings to be marked blue for all accessible spaces per AMC 21.07.090 J.10

Traffic review incomplete pending submission of additional drawings. R Ribble 5-3-22