Permit Number: C22-1386
Permit Type: Commercial Building Permit - None BldgAlter
Address: 1700 HILLCREST DR Anchorage
Location: WEST HIGH SCHOOL PHASE II (REF. C21-1333, PH 1)
Work Description: ***THIS PERMIT IS FOR PHASE II OF PERMIT #C21-1333***
DEMO & REPLACE HYDRONIC, DOMESTIC WATER, GAS, AND FDC PIPING; DEMO OF ABANDONED IN-PLACE MECHANICAL & ELECTRICAL. DEMO & REPLACE SLAB WITH FINISHES. - MDR
Status: Closed
Project Name: WEST HIGH SCHOOL: WEST & ROMIG SCHOOL SITE TR 1A
Review Type: Structural
Result: Correction
Result Date: 5/3/2022 1:36:31 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

2022/05/03 - Initial review complete. Comments issued.


1. Please provide at least one set of plans that meet the minimum 3/32" text size per AMC § 23.10.104.10.1.

 2022/05/03 - Comment resolved. Full-size plans submitted.


2. Please provide a letter from the Owner indicating who they will be hiring to provide the special inspections for this project. The special inspectors must be licensed by the Municipality of Anchorage in the types of inspections to be performed. [Reference: IBC 2018 § 1704.2, AMC § 23.15.1703.7]