Permit Number:
C22-1083
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
4600 POSTMARK DR Anchorage
Location:
Work Description:
REMODEL OF EXISTING INTERIOR SPACE WITHIN THE ANC NORTH TERMINAL, TO INCLUDE MEP - ADB
Status:
Issued
Project Name:
ANC NORTH TERMINAL
Review Type:
Fire
Result:
Approved
Result Date:
2/22/2022 4:15:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
1) Provide a smoke/flame spread rating for the felt being used in the ceilings.
2
_
Resolved
2) Occupant calculation is 150 sq ft per occupant in the 2018 IBC. You have it for 100 which is in the 2012 IBC.
3
_
Resolved
3) The crew briefing is listed as a B occupancy, should this be for unfixed tables and chairs under table 1004.5 for the 2018 IBC.
4
_
Resolved
4) The experience theater is listed as occupant factor of 59, change to appropriate factor.
5
_
Resolved
5) Provide a door hardware schedule.
6
_
Resolved
6) Provide information on rated assembly walls and doors as needed.
7
_
Resolved
7) Some fire extinguishers are shown however not in the new area so it is hard to establish travel distance and and square footage per extinguisher.
8
_
Resolved
8) No exit signs shown out of theater, it appears that would be a two exit space.
9
_
Resolved
9) Two exits shown out of theater however the exit sign placement at the exit into the hall does not reflect the correct direction.
Advisory Information: