Permit Number: C22-1083
Permit Type: Commercial Building Permit - None BldgAlter
Address: 4600 POSTMARK DR Anchorage
Location:
Work Description: REMODEL OF EXISTING INTERIOR SPACE WITHIN THE ANC NORTH TERMINAL, TO INCLUDE MEP - ADB
Status: Issued
Project Name: ANC NORTH TERMINAL
Review Type: Fire
Result: Correction
Result Date: 2/8/2022 3:08:00 PM

Comments:

 Code SectionReview CommentStatus
1_
1) Provide a smoke/flame spread rating for the felt being used in the ceilings. 

2_
2) Occupant calculation is 150 sq ft per occupant in the 2018 IBC. You have it for 100 which is in the 2012 IBC. 

3_
3) The crew briefing is listed as a B occupancy, should this be for unfixed tables and chairs under table 1004.5 for the 2018 IBC. 

4_
4) The experience theater is listed as occupant factor of 59, change to appropriate factor. 

5_
5) Provide a door hardware schedule. 

6_
6) Provide information on rated assembly walls and doors as needed. 

7_
7) Some fire extinguishers are shown however not in the new area so it is hard to establish travel distance and and square footage per extinguisher. 

8_
8) No exit signs shown out of theater, it appears that would be a two exit space. 

9_
9) Two exits shown out of theater however the exit sign placement at the exit into the hall does not reflect the correct direction. 