Permit Number: C20-1336
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:

COMM T/I TO INCLUDE RENOVATION TO THE EXISTING EXCALATOR ENCLOSURE THAT CONNECTS THE PUBLIC PARKING GARAGE TO THE AIRPORT TERMINAL. TO INCLUDE REMOVING THE EXISTING STEEL AND GLASS ENCLOSURE AND CONSTRUCTING NEW AND /P/M/E - BWP

COVID-19 DISCOUNT 25% APPLIED

Status: Closed
Project Name: ANCHORAGE INTERNATIONAL AIRPORT
Review Type: Architectural
Result: Approved
Result Date: 6/14/2021 9:24:48 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker

Phone: 343-8391

Email: ParkerRW@muni.org

Project: ANCHORAGE INTERNATIONAL AIRPORT

Review Number: 471478

1) STATUS: 4/30/2020 Comments to be addressed.                     6/14/2021 APPROVED.


2) The following comments based upon the 2012 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.                     RESOLVED 6/14/2021.


3) T0.1                      The currently adopted version of the National Electric Code (NEC) is 2017.              RESOLVED PER RE-SUBMITTAL RECEIVED 6/11/2021.


4) T0.1                      The 2012 INTERNATIONAL ENERGY CONSERVATION CODE is to be included in the list of applicable codes affecting this project.                                    RESOLVED PER RE-SUBMITTAL RECEIVED 6/11/2021.



5) A2.2                      Key Sheet Note #6 states: "NEW AL. CURTAIN WALL SYSTEM W/ 1" THERMAL GLAZING". Please specify the thermal "U" factor that will meet the requirements of IECC Table C402.3 plus local amendment.                      RESOLVED PER RE-SUBMITTAL RECEIVED 6/11/2021.



6) A6.1 & A4.1           Provide structural and seismic calculations plus fastening details for the suspended circular ceiling decorations to include the engineers stamp and signature, for structural review on a deferred submittal basis.                              RESOLVED PER RE-SUBMITTAL RECEIVED 6/11/2021.


 

7) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.  (23.10.104.8.1)                            RESOLVED 6/14/2021.