DEMO & REPLACE HYDRONID, DOMESTIC WATER, GAS, AND FDC PIPING PLUS DEMO OR RELOCATION OF ABANDONED-IN-PLACE/EXISTING PLUMBING PIPING & ELECTRICAL CONDUIT IN UTILIDOR AREAS. ALSO INCLUDES DEMO & REPLACE OF SLAB ON METAL DECK WITH FINISHES AND REPAIR OF EXISTING FIREWALLS IN THE UTILIDOR - BWP
2 PHASE PLAN - SEE PHASING PLAN
***THIS PERMIT WAS INCORRECTLY CLOSED BEFORE THE PHASES WERE COMPLETE. A NEW PERMIT WILL BE ISSUED AND ROUTED TO THE SAME REVIEWERS WITHOUT ANY FEES*** - MDR 4/22/2022
Reviewed by: Bergstrom, Leigh W.
Phone: 343-8326
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: ParkerRW@muni.org
Project: WEST HIGH SCHOOL
Review Number: 468350
1) STATUS: 4/23/2021 Comments to be addressed. 4/29/2021 APPROVED.
2) The following comments based upon the 2018 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. RESOLVED 4/29/2021.
3) M0.01 GENERAL NOTE I Clarify the use of PPL piping as a UPC approved material for domestic water installations. RESOLVED PER RE-SUBMITTAL RECEIVED 4/29/2021.
4) M2.01 thru M2.04 There are multiple locations where new plastic piping will be penetrating fire walls in the utilidors. Provide details for "Through-penetration firestop systems" rated for up to 2-1/2" plastic pipe in accordance with IBC 714.4.1.2. RESOLVED PER RE-SUBMITTAL RECEIVED 4/29/2021.