DEMO & REPLACE HYDRONID, DOMESTIC WATER, GAS, AND FDC PIPING PLUS DEMO OR RELOCATION OF ABANDONED-IN-PLACE/EXISTING PLUMBING PIPING & ELECTRICAL CONDUIT IN UTILIDOR AREAS. ALSO INCLUDES DEMO & REPLACE OF SLAB ON METAL DECK WITH FINISHES AND REPAIR OF EXISTING FIREWALLS IN THE UTILIDOR - BWP
2 PHASE PLAN - SEE PHASING PLAN
***THIS PERMIT WAS INCORRECTLY CLOSED BEFORE THE PHASES WERE COMPLETE. A NEW PERMIT WILL BE ISSUED AND ROUTED TO THE SAME REVIEWERS WITHOUT ANY FEES*** - MDR 4/22/2022
Reviewed by: Bergstrom, Leigh W.
Phone: 343-8326
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: ParkerRW@muni.org
Project: WEST HIGH SCHOOL
Review Number: 467887
1) STATUS: 4/23/2021 Comments to be addressed.
2) The following comments based upon the 2018 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.
3) M0.01 GENERAL NOTE I Clarify the use of PPL piping as an IMC approved material for hydronic installations.
4) M2.01 thru M2.04 There are multiple locations where new plastic piping will be penetrating fire walls in the utilidors. Provide details for "Through-penetration firestop systems" rated for up to 8" plastic pipe in accordance with IBC 714.4.1.2.