Permit Number: C21-1231
Permit Type: Commercial Building Permit - Building Sign
Address: E 300 DIMOND BLVD Anchorage
Location: SUITE 100
Work Description: INSTALL 1 ELECTRIC SIGN -KSH
CONTRACTOR ASSIGNED TO GLACIER SIGN & LIGHTING PER MICHAEL DROEGE; CENTRY 21 - 8/22/2022
**CONTRACTOR TRANSFER TO UNIVERSAL SIGN & LIGHTING PER MICHAEL DROEGE; CENTURY 21** 9/27/2022 - MDR
Status: Issued
Project Name: SIGN- CENTURY 21 REALTY SOLUTIONS
Review Type: Structural
Result: Correction
Result Date: 4/8/2021 9:15:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Permit C21-1231 Reviewed under IBC 2018 and local amendments.

Permit Manager: Kateryna Hile, 343-8339,Kateryna.Hile@anchorageak.gov

Reviewer: Ralph Jordan, 343-8371, ralph.jordan@anchorageak.gov


Structural comments 4/8/21:

1. Please provide method of attachment for sign/letters. Provide detail or description showing material attached to, (wood studs, concrete, masonry) and size, number of fasteners and minimum embedment.

Provide approximate weight of sign, or show calculations verifying that attachment can carry gravity, seismic and wind loads.


Please address above comment fully, and provide submittal (can be existing drawings redlined) to the permit manager. Further review may be required.