Permit Number: X21-1036
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: ALTERNATE MEANS
Status: Closed
Project Name: Change Order of Bldg App C20-1166
Review Type: Electrical
Result: Approved
Result Date: 2/5/2021 11:06:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

The electrical blanket provided is acceptable and the change order is approved.


----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

Electrical Comments

 

Reviewed by: David Abuobaid                                                 Permit #: C20-11166 (X21-1036)

Phone: 343-8333                                                                      Date: 2/2/2021

Fax:     249-7775                                                                      

Email:  AbuobaidDH@muni.org

Permit Manager: Bob Parker

Phone: 343-8391

Email:  Parkerrw@muni.org

Project: ANC Airport Transfer Switch Replacement (Fax: no fax provided)

____________________________________________________________________________________  
1. The following comments based on the 2017 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the NEC or any federal, state or local regulations.

     

      2. CHANGE ORDER # X21-1036

      Please provide the detail rating on non conductive curtain that is intended to be used to in front of new

      277V line to ground transfer switch installation to change classification to condition 1 to meet current

      code.

  

     3. When the above comments have been addressed, please update the electrical plans at the MOA Plans

     Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical  

     engineers stamp and signature.  

 

 