EPLANS - REPLACE 4 EXISTING EXPLOSIVE DETECTION SCANNERS IN CONCOURSE B AND 1 IN NORTH TERMINAL TO INCLUDE ELECTRIC - BWP
COVID-19 DISCOUNT 25% APPLIED
Permit #: C20-1504
Date: 2020 July 14
____________________________________________________________________________________
PERMIT STATUS
2020/07/14 – Initial review complete. Comments issued.
1. SEISMIC RESTRAINTS
What is the weight of the new baggage scanning equipment? These likely need a seismic anchorage design by a structural engineer registered in the state of Alaska.
[Reference: ASCE 7-10 § 13.3]
2. STRUCTURAL REVIEW
Sheet B8.00 seems to have structural loading criteria for review by a structural engineer. Please provide the engineering analysis, or clarify the intent.