Permit Number: X20-1387
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: WATER HEATER PLATFORM AND ATTACHMENT
Status: Closed
Project Name: Change Order of Bldg App C20-1046
Review Type: Structural
Result: Correction
Result Date: 7/7/2020 11:03:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Review #1 7/7/20 X20-1387/C20-1046 Deferred submittal for water heater platform and strapping and RTU curb attachment

Reviewer: Ralph Jordan, 343-8371 ralph.jordan@anchorageak.gov

Permit Managers, 343,8211


Advisory Comment: Review based on IBC 2012 and local amendments. This review does not permit the violation of the building codes or any governmental regulation.


Structural Comments:


1. Although the submitted calculations appear adequate, no drawings indicate the work to be approved so that an inspector can verify the callouts that appear in structural calcs.

Please provide drawings or sketch showing work to be done. Callout stud framing, strapping, RTU fasteners and spacing on plans. If using existing drawings submit redlines to be approved.  