Permit Number: C20-1361
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3901 OLD SEWARD HWY Anchorage
Location:
Work Description: MINOR EXTERIOR WORK AND PHASED INTERIOR ALTERATIONS ON BOTH FIRST FLOOR AND MEZZANINE, INCLUDING CHANGES TO THE LAYOUT OF EXISTING OFFICE SPACES AND RECONFIGURATION OF MEP AS NECESSARY-GJS

COVID 19 DISCOUNT APPLIED
Status: Closed
Project Name: DMV OFFICES
Review Type: Fire
Result: Correction
Result Date: 5/22/2020 3:42:59 PM

Comments:

 Code SectionReview CommentStatus
1_
CODE STUDY - MANUAL FIRE ALARM BOXES 
The code study notes that manual fire alarm boxes are not required for buildings equipped throughout with an automatic sprinkler system complying with Section 903.3.1.1. Please note that the local amendment deletes the exception to Section 907.2.2. Please revise accordingly. 
Reference: AMC 23.45.907.2.2


2_
ADVISORY
The architectural reflected ceiling plans do not indicate the locations of required exit signage. The electrical plans show the locations but there is no confirmation by the architect that the locations are correct. 
Reference: IFC Section 105.4.2, 1011.1; AS 08.48.221





Advisory Information:

- Review for electrical scope of work only // PANILO