REMOVAL OF ROOF WATERPROOFING LAYER, INSULATION AND ROOF DRAINS. INSTALL NEW ROOFING, INSULATION, ROOF DRAINS AND RAISE PARAPET WALLS - MJD
COVID-19 25% DISCOUNT APPLIED
Reviewed by: Bergstrom, Leigh W.
Phone: 343-8326
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Melissa Davidson
Phone: 343-8339
Email: DavidsonMJ@muni.org
Project: ARH ROOF REPLACEMENT
Review Number: 448790
1) STATUS: 5-19-2020 Comments to be addressed.
2) The following comments based upon the 2012 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.
3) A002 The occupancy group for a hospital is "I-2". (IBC 308.4)
4) A002 The building is at least 6 stories. "I-2" in a 6 story building requires Type "1A" construction. (IBC Table 503)
5) A002 Type "1A" construction is not a 1 hour rated structure. Provide the Fire-Resistance Rating Requirements for Type "1A" Construction per IBC Table 601.
6) A111 Sheet Note D9 (two locations) states: "Demolish existing door and frame." On sheet A201 for the new work, the replacement or fix is not addressed. Please clarify.