Permit Number: C20-1336
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:

COMM T/I TO INCLUDE RENOVATION TO THE EXISTING EXCALATOR ENCLOSURE THAT CONNECTS THE PUBLIC PARKING GARAGE TO THE AIRPORT TERMINAL. TO INCLUDE REMOVING THE EXISTING STEEL AND GLASS ENCLOSURE AND CONSTRUCTING NEW AND /P/M/E - BWP

COVID-19 DISCOUNT 25% APPLIED

Status: Closed
Project Name: ANCHORAGE INTERNATIONAL AIRPORT
Review Type: Structural
Result: Correction
Result Date: 6/3/2020 8:12:36 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

PERMIT STATUS
6/3/2020 - Permit reviewed. Comments issued.
6/24/2021 - Responses reviewed. Comments issued.

1. Please provide a letter from the Owner indicating who they will be hiring to perform the special inspections on this project. This special inspections must be licensed in the types of inspections to be performed.

Comment remains. No letter provided. BBFM response indicates R&M Consultants, but no letter provided verifying this. WAB - 6/24/2021

2. DRAWING CLARIFICATIONS
Reference the drawings. Please provide the following:

A. Reference sheet S5.3. A few of the details on this sheet call for post installed anchors but do not appear to call out embedment depth. Please clarify.
Item resolved. This information has been provided. WAB - 6/24/2021
B. Reference details 7 and 8 on sheet S5.3. Please provide the gusset size and show that it meets the dimensional requirements of AISC 360-10 Chapter D.
Item remains. The response appears to assume this is a comment about capacity. This is not the case. There are prescriptive requirements in Chapter D for dimensions on single bolt connections. These dimensional requirements cannot be verify because dimensions have not been provided on the drawings. Please provide. WAB - 6/24/2021