Reviewed by: Bergstrom, Leigh W.
Phone: 343-8326
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Andrew Earp
Phone: 343-8338
Email: Earpal@muni.org
Project: CONNOCO PHILLIPS GATE "L" TICKETING
Review Number: 447063
1) STATUS: 4-13-2020 Comments to be addressed. 4-17-2020 APPROVED.
2) The following comments based upon the 2012 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations. RESOLVED 4-17-2020.
3) This change order apparently eliminates the janitor's closet and the service sink. Provide revised plumbing plans as well as the plumbing fixture schedule. RESOLVED PER RE-SUBMITTAL RECEIVED 4-16-2020.
4) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1) RESOLVED 4-17-2020.