REPLACE AND RELOCATE SERVER ROOM A/C UNIT. EXTEND HEAT REJECT PIPING TO NEW LOCATION, REPLACE PUMP P-28 WITH LIKE PUMP, EXTEND ELECTRICAL CONDUIT TO NEW LOCATION AND UTILIZE EXISTING BREAKERS, CONTROLLERS, AND DISCONNECTS - BWP
COVID-19 DISCOUNT 25% APPLIED
ELECTRICAL PLAN REVIEW STATUS:
The electrical plans have been reviewed and approved.
------------------------------------------------------------------------------
Electrical Comments
Reviewed by: David Abuobaid Permit #: M20-1298
Phone: 343-8333 Date: 4/23/2020
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: Parkerrw@muni.org
Project: Conoco Philips (Fax: no fax provided)
____________________________________________________________________________________
EQUIREMENT OF ELECTRICAL SCOPE OF WORK:
Please provide the electrical scope of work and include wiring method, existing service load calculations, panel schedules with connected and demand loads, one-line diagram, and accessibility to overcurrent protection so we can determine if work requires 100% designed engineered drawing by a registered professional electrical engineer of the State of Alaska.