A5.02, 1 and A5.06,5:A vertical grab bar is also required on the side wall of the ADA water closet. (ICC/ANSI A117.1-604.5.1)
NOT RESOLVED
A4.0 thru A4.6; Show foundation insulation R-10 to at least 3 feet in depth.
MOSTLY RESOLVED: Foundation insulation, R-10 to at least 3 feet in depth, is now shown on most detail. Note that the drawing numbers have changed.
A0.01, Applicable Codes: The applicable codes and edition are as follows;
International Existing Building Code (IEBC) 2012 and local amendments
International Residential Code (IRC) 2012 and local amendments
International Fire Code (IFC) 2012 and local amendments
International Mechanical Code (IMC) 2012 and local amendments
International Fuel Gas Code (IFGC) 2012 and local amendments
International Energy Conservation Code (IECC) 2012 and local amendments
Uniform Plumbing Code (UPC) 2012 and local amendments
National Electric Code (ICC/NEC/NFPA 70) 2017 and local amendments
Accessible and Useable Buildings and Facilities (ICC/ANSI A117.1) 2009
MOSTLY RESOLVED: Please add the following that were missed.
A0.01, Several of the section/table reference numbers are applicable to the 2009 I codes. Please revise to cite the applicable 2012 edition.
RESOLVED.
A0.01, The required Building Element Ratings are correct as shown. Please clarify why some of the provided are less that required.
NOT RESOLVED:
This is now shown on G0.1; however, it still requires correction.
A0.01, Please address these additional items in the Code Study Items:
Add the public spaces occupant loads (Sec 1004)
Add Energy Code insulation requirements, including the foundation; reference; IECC Chapter 4 and local amendments)
Add the public spaces plumbing fixture count, i.e., required/provided; reference; Section 2902, Table 2902.1
Add the Guestroom Matrix the ADA count, i.e., required/provided; reference; Section 1107.6, Table 1107.6.1.1
A0.01, Means of egress: Add the common path of egress requirement; reference; Section 1014.3, Table 1014.3
The Construction Requirements identifies an A-5 occupancy; however, the Building Area Summary identifies an A-2 occupancy. Please clarify. Some areas actually appear to be an A-3 occupancy.
A2.05, Roof Plan; The two access hatches appear to be located within 10 feet of the roof edge. If so, indicate 42" high guards at the roof edge, reference Sec 1013
This is still not corrected. Please revise the roof hatch locations to greater than 10 feet of the roof edge or indicate 42" high guards at the roof edge.
A1.01, Add a fire door at the east end of the residential corridor on the first floor, or continue the corridor 1/2 hour F R rating all the way out to the second exit.
NOT FULLY RESOLVED:
Check direction of door swings and continuity of the corridor 1/2 hour F R rating all the way out to the second exit.
All drawings: The drawings still indicate 60% complete and F&F submittal. Please provide a full permit set of drawings.
MOSTLY RESOLVED:
Although the drawings indicate 60% complete and F&F submittal, the local Architect has informed me that in fact this is the full permit submittal set. This will be corrected on the next drawing submittal.