Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C20-1046
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: CINNABON INTERIOR T/I LOCATED IN SUITE 119 - MJD
Status: Closed
Project Name: CINNABON
Review Type: Mechanical
Result: Correction
Result Date: 3/4/2020 1:13:27 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.

Phone: 343-8326

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Melissa Davidson

Phone: 343-8339

Email: DavidsonMJ@muni.org

Project: CINNABON

Review Number: 445089


1) STATUS: 2-24-2020 Comments to be addressed.                     3-04-2020 COMMENTS TO BE ADDRESSED.


2) The following comments based upon the 2012 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.                 RESOLVED 3-04-2020.


3) Provide structural and seismic calculations plus fastening details for Hood 1 and the 50 gallon water heater to include the engineers stamp and signature for structural review on a deferred submittal basis.                    RESOLVED 3-04-2020.


4) M-2                 There is no grease duct in this project. Delete the paragraph.               RESOLVED PER RE-SUBMITTAL RECEIVED 2-27-2020.


5) M-2                 Plastic vent and domestic water piping are not permitted above the drop ceiling as this is a return air plenum per IMC 602.2.1. Please clarify.                            RESOLVED PER RE-SUBMITTAL RECEIVED 2-27-2020.


6) 1/M-5              With 2000 CFM supplied to the space and 2000 CFM return air to the existing AC unit, there is no provision for outside air. Please clarify the minimum outside air setting required for the AC unit.                        3-04-2020 UNRESOLVED. THE ISSUE WAS NOT MAKEUP AIR FOR THE HOOD, RATHER VENTILATION AIR FOR THE TENANT SPACE PER IMC 403. PROVIDE THE MINIMUM OUTSIDE AIR SETTING REQUIRED PER IMC 403 VIA THE EXISTING 8" x 8" OUTSIDE  AIR CONNECTION TO THE AC UNIT AND DECREASE THE RETURN AIR VOLUME ACCORDINGLY.


7) When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1)

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter