Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C20-1158
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: INSTALL 1 NEW PEDESTRIAN BOARDING BRIDGE AND REPLACE 1 PEDESTRIAN BOARDING BRIDGE AT THE B CONCOURSE WITHIN TED STEVENS INTERNATIONAL AIRPORT, PAVING MARKING MODIFICATIONS.
Status: Closed
Project Name: CONCOURSE PBB (BRIDGE)
Review Type: Structural
Result: Correction
Result Date: 3/11/2020 10:21:22 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

STRUCTURAL REVIEW COMMENTS


Permit #: C20-1158

Project: Ted Stevens International Airport Passenger Boarding Bridges

Date: March 10, 2020

_________________________________________________________________________________

REVIEW STATUS

03/10/20 – Initial review complete; additional submittals are required.


This review is based on the requirements of the Anchorage Municipal Code (AMC), 2012 International Building Code (IBC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.


1. Drawing Sheet S5 shows the installation of a new passenger boarding bridge at Gate B8 utilizing an existing foundation. There is no description of the foundation’s construction or ability to carry the loads of the new boarding bridge. Please provide verification of it’s construction and a statement of its adequacy for the proposed installation.


Please address each comment and include one copy of additional/revised calculations and two copies of additional/revised drawings. Please indicate the location of any additions or corrections in the response; additional review comments may be generated. All documents should be submitted to the permit manager as shown above.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS