Electrical Comments
Reviewed by: David Abuobaid Permit #: C20-1158
Phone: 343-8333 Date: 2/28/2020
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Andrew Earp
Phone: 343-8338
Email: EarpAL@muni.org
Project: Ted Stevens International (Fax: no fax # provided)
____________________________________________________________________________________ 1. The following comments based on the 2017 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the NEC or any federal, state or local regulations.
2. CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION ON FLOOR PLAN & PANEL SCHEDULES:
Sheet E8 of E8 (Panel Schedules and Floor Plans Circuit Identifications). Panel schedules have many circuits named escalator and L1 LTS BAG Screen. Please note that these circuits should be individually identified with their locations on floor plans and on the panel schedules according to NEC 408.4 for circuit identifications.
3. When the above comments have been addressed, please update the electrical plans at the MOA Plans Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical engineers stamp and signature.