Permit Number: C20-1046
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: CINNABON INTERIOR T/I LOCATED IN SUITE 119 - MJD
Status: Closed
Project Name: CINNABON
Review Type: Architectural
Result: Correction
Result Date: 2/11/2020 10:49:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Architectural Comments

 

Reviewed by: David Abuobaid                                                 Permit #: C20-1046

Phone: 343-8333                                                                      Date: 2/24/2020

Fax:     249-7775                                                                      

Email:  AbuobaidDH@muni.org

Permit Manager: Melissa Davidson

Phone: 343-8339

Email:  Pdavidsonmj@muni.org

Project: Cinnabon (Fax: no fax #)

____________________________________________________________________________________   

1. The following comments based upon the 2012 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations. 

 

2. EXITING DOOR:

Sheet A2. The plans show no exiting provided.

Please revise the plans and show the exiting door /grill door.   

 

3. When the above comments have been addressed, please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, engineers stamp and signature. 

 