Location: ALOFT HOTEL, 146 ROOMS
Work Description: NEW CONSTRUCTION HOTEL (63,194 SQFT R-1 OCC. VA CONST.) (21,774 SQFT A-2 OCC. VA CONST).  TOTAL SQUARE FOOTAGE 84,968, 146 ROOMS - MJD
Status: Issued
Project Name: ALOFT HOTEL
Review Type: Architectural
Result: FandF
Result Date: 2/12/2020 4:20:00 PM

Comments:

 Code SectionReview CommentStatus
1_
A5.02, 1 and A5.06,5:A vertical grab bar is also required on the side wall of the ADA water closet. (ICC/ANSI A117.1-604.5.1)

2_
A4.0 thru A4.6; Show foundation insulation R-10 to at least 3 feet in depth.

3_

A0.01, Applicable Codes: The applicable codes and edition are as follows;


International Building Code (IBC) 2012 and local amendments


International Existing Building Code (IEBC) 2012 and local amendments


International Residential Code (IRC) 2012 and local amendments


International Fire Code (IFC) 2012 and local amendments


International Mechanical Code (IMC) 2012 and local amendments


International Fuel Gas Code (IFGC) 2012 and local amendments


International Energy Conservation Code (IECC) 2012 and local amendments


Uniform Plumbing Code (UPC) 2012 and local amendments


National Electric Code (ICC/NEC/NFPA 70) 2017 and local amendments


Accessible and Useable Buildings and Facilities (ICC/ANSI A117.1) 2009




4_
A0.01, Several of the section/table reference numbers are applicable to the 2009 I codes.  Please revise to cite the applicable 2012 edition.

5_
A0.01, The required Building Element Ratings are correct as shown.  Please clarify why some of the provided are less that required.

6_

A0.01, Please address these additional items in the Code Study Items:


Add the public spaces occupant loads (Sec 1004)

Add Energy Code insulation requirements, including the foundation; reference; IECC Chapter 4 and local amendments)

Add the public spaces plumbing fixture count, i.e., required/provided; reference; Section 2902, Table 2902.1

Add the Guestroom Matrix the ADA  count, i.e., required/provided; reference; Section 1107.6, Table 1107.6.1.1



7_
A0.01, Means of egress: Add the common path of egress requirement; reference; Section 1014.3, Table 1014.3

8_
The Construction Requirements identifies an A-5 occupancy; however, the Building Area Summary identifies an A-2 occupancy.  Please clarify.  Some areas actually appear to be an A-3 occupancy. 

9_
A2.05, Roof Plan; The two access hatches appear to be located within 10 feet of the roof edge.  If so, indicate 42" high guards at the roof edge, reference Sec 1013

10_
A1.01, Add a fire door at the east end of the residential corridor on the first floor, or continue the corridor 1/2 hour F R rating all the way out to the second exit.