Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
C19-2451
Permit Type:
Commercial Building Permit - None BldgCombo
Address:
W 601 5TH AVE Anchorage
Location:
Work Description:
EPLANS- 35,492 SQFT ADDITION, TYPE IB,OCCUPANCY B, WITH AN ALTERATION OF EXISTING BUILDING
**CONTRACTOR PAID FOR 9 ADDITIONAL INSPECTIONS 8/15/23 - WENT OVER 200 BY 9 - BWP**
Status:
Closed
Project Name:
EPLANS KEY BANK
Review Type:
Fire
Result:
Correction
Result Date:
2/14/2020 5:53:55 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
See https://eplans.muni.org for comments // PANILO
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501