Permit Number:
C19-2451
Permit Type:
Commercial Building Permit - None BldgCombo
Address:
W 601 5TH AVE Anchorage
Location:
Work Description:
EPLANS- 35,492 SQFT ADDITION, TYPE IB,OCCUPANCY B, WITH AN ALTERATION OF EXISTING BUILDING
**CONTRACTOR PAID FOR 9 ADDITIONAL INSPECTIONS 8/15/23 - WENT OVER 200 BY 9 - BWP**
Status:
Closed
Project Name:
EPLANS KEY BANK
Review Type:
Electrical
Result:
Approved
Result Date:
1/28/2020 3:56:00 PM
Comments:
Code Section
Review Comment
Status
Advisory Information:
ELECTRICAL PLAN REVIEW STATUS:
The correction comments are addressed.
The electrical plans have been reviewed and approved.
-----------------------------------------------------------------------------------------------------------------------
9/24/2020
It appears that the building is intended to be occupied when the utility power is out. Since the service is 3000 A and the generator 400KW is complying with NEC 701.27. Please show the load shedding to keep the generator, controller, lighting and power continue working.
------------------------------------------------------------------------------------------------------------------------
Electrical Plan Review Status:
The electrical plans has been reviewed and approved.
-----------------------------------------------------------------------------------------------
Electrical Plan Review Status:
The electrical e-plans is provided with correction on the e-plans.
ADA Compliance